Model |
COU-48HZDR4 |
Outdoor Power Supply |
V/Ph/Hz |
380~415/3/50 |
Cooling |
Power Input |
W |
1000-4850-5700 |
Current Input |
A |
2.5-10.8-14.3 |
Heating |
Power Input |
W |
1100-4820-5900 |
Current Input |
A |
2.8-10.3-14.8 |
Max. Power Input |
W |
6100 |
Max. Current Input |
A |
9.9 |
Compressor |
Model |
|
MVB40FJLMC-L |
Type |
|
DC/Twin-Rotary |
Frequency Range |
rps |
12-121 |
Capacity |
W |
13250 |
Input |
W |
4150 |
Current (RLA) |
A |
15.4 |
Fefrigerant Oil |
ml |
FW68X/1250 |
Outdoor Fan Motor |
Model |
DR-310-100-8-2 |
Power Output |
W |
100 |
Speed |
r/min |
870 |
Insulation Class |
B |
Outdoor Coil |
Number of Row |
2 |
Tube Pitch(a)Xrow Pitch |
mm |
25×21.65 |
Fin Spacing |
mm |
1.6 |
Fin Type |
Hydrophilic |
Tube Outside Dia. And Type |
mm |
9.52 |
Inner Grooved |
Coil Length x Height x Width |
mm |
995x1350x43.3 |
Number of Circuits |
7 |
Outdoor Air Flow (Heigh Speed) |
m³/h |
6100 |
Outdoor Noise Level |
Power Level |
dB(A) |
68 |
Pressure Level |
58 |
Outdoor Unit |
Dimension (WxHxD) |
mm |
1015x1430x450 |
Package (WxHxD) |
mm |
1095x1545x485 |
Net/Gross Weight |
kg |
109/123.6 |
Refrigerant Type/Quantity |
g |
R32/3800 |
Throttle Part |
EXV |
Design Pressure |
MPa |
4.5/1.6 |
Max Pressure |
MPa |
4.5 |
Connection Wire |
Power Wiring |
mm² |
5×2.5 |
Signal Wiring |
mm² |
4×1.5 |
Refrigerant Piping |
Liquid Side/Gas Side |
mm |
ɸ9.52/ɸ15.88 |
Max. Pipe Length |
m |
65 |
Max. Hight Deop |
m |
30 |
Ambiertn Temperature |
Cooling |
ᵒC |
-15~50 |
Heating |
ᵒC |
-15~30 |
Reviews
There are no reviews yet.